Is it worth leaving your EV at an 11 kW AC charger for, say, 2 hours instead of buying a parking ticket? The calculator compares the parking fee with the charging cost, including the idle fee after 3 hours.

This example uses real rates from Bottrop, Germany: prices in euros, charging on the European three-phase grid (230/400 V).

Calculator

Parking ticket or charger?

Calculation: locally in your browser

15 min2 h4 h6 h8 h
€/h
6 A8101316 A
kWh
Charging price

Idle fee of 10 ct/min from the 181st minute of connection time.

* These kWh prices apply only with the “ELE Autostrom mobil” plan for ELE customers. The plan costs €3.99 per month; this amount is not included in the calculation.

More assumptions

The calculator credits the charged energy at your home electricity price, since you would otherwise have to charge it at home. With 0 ct it compares the full cost at the charger with the parking ticket.

Result
–
–
Parking ticket – –
Charger, minus home electricity – –
Cost at the charger
Electricity –
Idle fee –
Parking fee at the charger–
Total at the charger –
Home electricity credit –
Effective cost of parking at the charger–

* Applies only with the “ELE Autostrom mobil” plan for ELE customers (€3.99/month, not included).

Charging power––
Charged––
Range––
Battery full after––
Trend

Cost over parking duration

–

Cost of parking ticket and charger depending on parking duration Idle fee
Parking ticket Charger, minus home electricity Charger total (dashed)
Diagram 1

Phasor diagram: how 230 V becomes 400 V

The three phase-to-neutral voltages are each 230 V long and shifted by 120°. The line-to-line voltage U₁₂ = U₁ − U₂ connects the tips of two phasors.

Rotating phasor diagram with construction of the line-to-line voltage Circle r = 230 V (gray) · r = 400 V (blue) 120° −U₂ U₁ U₂ U₃ U₁₂ U₂₃ U₃₁ N Triangle N–L1–L2 with derivation U_L = √3 · U Triangle N – L1 – L2 120° 30° 230 V 230 V N L1 L2 U · cos 30° U · cos 30° U₁₂ = 2 · U · cos 30° cos 30° = √3 / 2 U₁₂ = √3 · U U₁₂ = 1.732 · 230 V U₁₂ ≈ 398 V ≈ 400 V ωt = 90° U₁₂ leads U₁ by 30°
ωt
Diagram 2

Instantaneous power with a balanced load

Each phase pulsates at twice the grid frequency. The sum of the three phases stays constant. The diagram takes current and cos φ from the calculator.

Instantaneous power p1, p2, p3 and their constant sum P = Σp Mean p₁ ωt (0 … 720°)
p₁(t) L1 p₂(t) L2 p₃(t) L3 p₁+p₂+p₃ = 3 · U · I · cos φ
Math

Step-by-step derivation

From complex phasors to the formula P = √3 · U · I · cos φ.

1

Phase voltages as phasors

U₁ = U·e^(j0°) · U₂ = U·e^(−j120°) · U₃ = U·e^(−j240°)

All three phasors have the same length (U = 230 V) and are 120° apart.

2

Difference of two phases

U₁₂ = U₁ − U₂ = U·[1 − (−½ − j·√3/2)] = U·(3/2 + j·√3/2)

The line-to-line voltage is the difference of two phase-to-neutral voltages.

3

Magnitude and angle

|U₁₂| = U·√(9/4 + 3/4) = U·√3
arg U₁₂ = arctan((√3/2)/(3/2)) = 30°

Geometrically: the triangle has a 120° angle at the apex, and the base angles are 30° each. It follows that U_L = 2·U·cos 30° = √3·U.

U_L = 1.732 · 230 V ≈ 398 V ≈ 400 V
4

Instantaneous power per phase

p₁(t) = u·i = U_Ph·I·[cos φ − cos(2ωt − φ)]

The power of each phase oscillates at 100 Hz around the mean value U_Ph·I·cos φ.

5

Sum of the three phases

Σ cos(2ωt − φ − k·240°) = 0  (k = 0, 1, 2)

The alternating components form a balanced three-phase system and cancel each other out.

P = p₁ + p₂ + p₃ = 3·U_Ph·I·cos φ
6

Substituting U_Ph = U_L/√3

P = 3·(U_L/√3)·I·cos φ = (3/√3)·U_L·I·cos φ
P = √3 · U_L · I · cos φ

At 16 A: √3 · 400 V · 16 A · 1 ≈ 11.1 kW. At 32 A: ≈ 22.2 kW.

In practice at the charger
  • φ is the angle between phase voltage and phase current, not between U_L and I. Modern on-board chargers reach cos φ ≈ 0.99.
  • 3 · 230 V and √3 · 400 V give slightly different values because 400 V / √3 = 230.9 V. Both nominal values are rounded.
  • The √3 formula only applies to a balanced load. Many vehicles charge on one or two phases. Then P = n · U_Ph · I · cos φ with n phases in use.
  • Billing is based on the energy measured at the charger’s meter, so you also pay for the charging losses in the vehicle.